A roof paint cooled a Singapore factory roof and rooms.

Roof‑cooling paint — Singapore

In 2026 field trials, sky‑cooling roof coatings delivered measured benefits on real buildings. On a Singapore factory, the paint cooled the roof surface by about 15.5 °C and cut roof heat‑flow from roughly 202 to 63.8 W/m², trimming peak indoor air temperature by about 1.1 °C. In full‑scale temporary houses, a radiative‑cooling coating reduced September cooling‑energy use by 21%. Together, these tests put numbers on building‑scale effects.

Why it’s interesting

Fig. 036 Upward waves from the coated roof side and many downward streams on the bare side encode the measured drop in roof heat‑flow from about 202 to 63.8 W/m² in the Singapore trial.

Why it’s interesting

It moves cool roofs from lab coupons to working buildings, with numbers facilities can plan around. It also shows the limit inside: big roof relief, small air change—unless more of the envelope is treated.

The longer version

These coatings work in two ways: they reflect sunlight and they radiate heat to the cold sky. In field measurements published May 15, 2026 (Building and Environment 296), a Singapore factory’s coated roof ran about 15.5 °C cooler around noon, and heat flowing into the roof dropped from roughly 202 to 63.8 W/m². Inside, peak air temperature fell by about 1.1 °C—modest, because only part of the envelope was treated and internal gains remained.

A full‑scale trial in temporary houses, published online in 2026 in Renewable Energy (vol. 276; issue dated Nov 15, 2026), measured a 21% reduction in September cooling‑energy demand after applying a radiative‑cooling coating. Independent field and modeling studies report similar surface‑cooling ranges (about 5–15 °C) and cooling‑energy cuts (roughly 20–35%), supporting these magnitudes while noting that performance depends on climate and sky conditions.

Edition
No. 036
Date
Wednesday 4 November 2026
Subject
Roof‑cooling paint
Locality
Singapore
Period
2026
Field
technology
Evidence
4 sources, 2 primary

See how we got here

Found after 26 research paths · Selected from 6 candidates

  1. 01 Hot roofs Sun drives strong heat gain into buildings.
  2. 02 Cool roofs Light coatings reflect sunlight to reduce heating.
  3. 03 Sky-cooling coatings They also radiate heat to the open sky.
  4. 04 Factory trial, Singapore Roof about −15.5 °C; heat‑flux 202→63.8 W/m²; indoor peak −1.1 °C.
  5. 05 Temporary houses trial Cooling‑energy use fell 21% in September after coating.
  6. 06 Urban canyon ranges Independent studies report 5–15 °C roof cooling; 20–35% energy cuts.
  7. → A roof paint cooled a Singapore factory roof and rooms.

Sources

Nothing publishes without independent sources. How we verify →

  1. 1
    The impact of radiative cooling paint on a factory building in tropics

    Elsevier (Building and Environment) · 2026 · peer reviewed Primary

    All factory metrics and the publication date (vol. 296; 15 May 2026; peak indoor −1.1 °C; roof surface −15.5 °C; heat‑flux 202→63.8 W/m²).

    sciencedirect.com

  2. 2
    Experimental and numerical investigation of cooling and energy-saving performance of a novel scalable radiative cooling coating in full-scale temporary houses

    IDEAS/RePEc (Elsevier Renewable Energy record) · 2026 · reference Primary

    Temporary‑house measurements including 21% September cooling‑demand reduction and free‑running indoor/exterior peak temperature drops; DOI 10.1016/j.renene.2026.126375.

    ideas.repec.org

  3. 3
    Experimental and numerical investigation of cooling and energy-saving performance of a novel scalable radiative cooling coating in full-scale temporary houses

    Elsevier (ScienceDirect listing) · 2026 · peer reviewed

    Confirms journal, volume (276) and issue date (15 Nov 2026) for the Renewable Energy article.

    sciencedirect.com

  4. 4
    Radiative cooling coatings and natural ventilation in urban street canyons: Synergies and trade-offs

    Elsevier (Building and Environment) · 2026 · peer reviewed

    Corroborates typical ranges for radiative‑cooling coatings (5–15 °C roof‑surface cooling; 20–35% cooling‑energy reduction) that align with the magnitudes reported in 2026 building‑scale trials.

    sciencedirect.com

Take it with you Challenge a friend ↗ SquareStoryWide Permanent link

THE DISPATCH / FROM ONE CURIOUS THING

CURIOSITY
IN YOUR INBOX.

Your dose of the unexpected, on your schedule.

One Curious Thing — one thing worth knowing, every day.

Enjoying these? Help keep the presses running.

Buy me a coffee Built By AndyBZ